I/O MODULE 16 digital inputs/outputs
61KZ010241 DIO 16
- 16 路数字量输入/输出, 软件可编程定义
- 类型 1 和类型 3 输入
- 最大输出电流: 500 mA /每路, 总共 8 A
- 过载电流和超过温度保护
- 状态和诊断 LED 显示
General data | |
---|---|
Housing dimensions (width x height x depth) | 22.5 mm x 99.0 mm x 114.5 mm |
Weight | 103 g (without connectors), 125 g (with connectors) |
Permissible operating temperature | +5° to +55°C |
Permissible storage and transport temperature | -25° to +85°C |
Permissible humidity | 10% to 95%, not condensing |
Permissible air pressure (operation) | 80 to 106 kPa (up to 2000 m above sea level) |
Permissible air pressure (storage and transport) | 70 to 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 according to IEC 60529 |
Connection method for connectors | Spring cage terminals |
Conductor cross-section (power connector) | 0.2 to 2.5 mm2 (24 – 12 AWG) |
Conductor cross-section (I/O connector) | 0.08 to 1.0 mm2 (28 – 18 AWG) |
Functional earth connection | To the DIN rail with spring contact |
Mode state visual indicators | Fault (FLT), status (STS) and power (PWR) LED lamps |
Power supply | |
---|---|
Main power supply VM | 24 V DC (-15% ÷ + 20% according to IEC 61131-2) |
Maximum allowed ripple | 5% of supply voltage (according to IEC 61131-2) |
Current consumption from main supply | 8 A max. |
Supply overvoltage protection on VM | Unidirectional Zener clamp (Vz > 30 V) |
Supply reverse polarity protection on VM | Input shunt diode, reverse connected |
Supply fuse | 12 A, not replaceable by the user |
Local bus power supply | 5 V DC (from local bus) |
Local bus supply protections | None |
Power presence visual indicators | Green LED lamp, lighted if main supply is present (PWR) |
Max. current on VS pin | 5 A max. |
Digital inputs | |
---|---|
Number of inputs | 16, software configurable |
Nominal input voltage | 24 V DC |
Nominal input current | 2.5 mA |
Common potentials | GND, common to all inputs |
Input design | According to IEC 61131-2 Type 1 and Type 3 (also Type 2 with external resistor) |
Maximum low-level threshold | VL,max < 5 V |
Minimum high-level threshold | VH,min > 11 V |
Permissible input voltage | -5 V ÷ +30 V (-24 V min. for 1 minute) |
Input protections | Protection over voltage transients and voltage reversing (see also digital outputs) |
Input reading delay | Depending on local bus cycle time |
Permissible cable length to the sensor | 30 m (to ensure conformance with EMC directive 89/336/EEC) |
Input state visual indicators | One orange LED lamp for every input, switched on if input level is high |
Digital outputs | |
---|---|
Number of outputs | 16, software configurable |
Nominal output voltage | 24 V DC |
Outputs rated current | 500 mA each |
Common potentials | GND, common to all outputs |
Output design | High-side MOSFET with inductive load Zener clamp |
Output voltage drop | < 1 V at rated current |
Nominal load (ohmic) | 48 Ω / 12 W |
Nominal load (lamp) | 12 W |
Nominal load (inductive) | 12 VA (load inductance < 1 H) |
Short circuit current | 1.7 A max. |
Output protection | Overload, short circuit, overtemperature |
Overload response | Auto restart |
Overload and short-circuit recovery time | Depending on board temperature |
Overtemperature recovery time | Depending on board temperature |
Inductive kickback behaviour | Zener clamp, integrated in output chip |
Output negative voltage | 52 V below Vm typical |
Output off to on switching delay | 150 μs max. (ohmic load) |
Output on to off switching delay | 200 μs max. (ohmic load) |
Output leakage current | 10 μA max. |
Permissive cable length to the load | 30 m (to ensure conformance with EMC directive 89/336/EEC). |
Output state visual indicator | One orange LED lamp for every output, switched on if output level is high |
Interface | |
---|---|
Local bus | Proprietary F3 IOs BUS |
Module address setting | With rotary switch on front panel |
Bus connections | By TBUS connectors on DIN rail |
Interface circuitry protections | ESD protections |
Level of ESD protection | ±8 kV (IEC 61000-4-2, contact discharge) |