上海丰林科技有限公司 上海浦东大道1139弄1号楼1305室 200135
电话: +86(0)21 5192 0512
, +86 (0)21 6247 4478-8012
sales@fltech.com.cn • 技术支持:roy.shen@fltech.com.cn

Shanghai Fenglin Technology Co.,Ltd. • Room 1305,No.1,335 Lane,
Pudong Avenue,Shanghai • 200135
Phone: +86 (0)21 5192 0513 : +86 (0)21 6247 4478 - 8012
sales@fltech.com.cn • technical: royshen@sh163.net

This site uses cookies to enable a better customer experience. By continuing to browse the site you are agreeing to our use of cookies.
Please find more information about cookies in our Data Privacy Statement.


Close

Partner In Automation

I/O MODULE 2 analog inputs for RTI

61KZ010246 RTI 2

  • 2 路标准 100Ω RTI (PT100) 的模拟量输入)
  • 两线和三线制传感器
  • 12 位分辨率
  • 状态和诊断 LED 显示

 Download datasheet
Datasheet download 资料下载

 

General data
Housing dimensions (width x height x depth)22.5 mm x 99.0 mm x 114.5 mm
Peso97 g (without connectors), 109 g (with connectors)
Permissible operating temperature+5° to +55°C
Permissible storage and transport temperature-25° to +85°C
Humidity10% to 95%, not condensing
Permissible air pressure (operation)80 to 106 kPa (up to 2000 m above sea level)
Permissible air pressure (storage and transport)70 to 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20 according to IEC 60529
Connection method for connectorsSpring cage terminals
Conductor cross-section (output connector)Da 0.2 a 1.5 mm2 (24 – 16 AWG)
Functional earth connectionTo the DIN rail with spring contact
Mode state visual indicatorsFault (FLT) and status (STS) LED lamps

 

Power supply
Power supply module5 VDC  and 24 VDC from local bus

 

Analog Inputs
Number of inputs2
Type of inputs                                                                For  standard PT100   Resistance  Temperature Detectors (RTDs), two and Three-wire 
Sensor temperature range (nominal)From -53° a + 358°C
Sensor resistance  range (nominal)from 79 Ω to 232 Ω
Sensor bias current-930 μA
Sensor cables resistance compensationYes, with three-wire sensors
Typical measuring tolerance at 25°C t.b.d.
Maximum measuring tolerance at 25°Ct.b.d.
Maximum error over temperaturet.b.d.
Outputs common potential isolation from GND500 VAC, funcitonal
Isolation between channelsNone
Input state visual indicatorsnone

 

Interface
Local busProprietary F3 IOs BUS
Moduli address settingWith rotary  switch on front panel
Bus connessionsBy  TBUS  connectors on DIN rail
Interface circuitry protectionsESD protections
Level of ESD protection±8 kV (IEC 61000-4-2, contact discharge)

 

© Copyright 2017 CANNON-Automata
中文网站 © Copyright 2018 上海丰林科技有限公司