I/O MODULE 2 analog outputs
61KZ010245 AO2V
- 2 路 模拟量输出,0-10 V 或 ±10 V
- 12 位分辨率
- 负载范围 (电压输出): 1 kΩ ~ ¥
- 状态和诊断 LED 显示
Datasheet download
Datasheet download 资料下载
General Data | |
---|---|
Housing dimensions (width x height x depth) | 22.5 mm x 99.0 mm x 114.5 mm |
Weight | 99 g (without connectors), 119 g (with connectors) |
Permissible operating temperature | +5° to +55°C |
Permissible storage and transport temperature | -25° to +85°C |
Permissible humidity | 10% to 95%, not condensing |
Permissible air pressure (operation) | 80 to 106 kPa (up to 2000 m above sea level) |
Permissible air pressure (storage and transport) | 70 to 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 according to IEC 60529 |
Connection method for connectors | Spring cage terminals |
Conductor cross-section (power connector) | 0.2 to 2.5 mm2 (24 – 12 AWG) |
Conductor cross-section (I/O connector) | 0.08 to 1.0 mm2 (28 – 18 AWG) |
Functional earth connection | To the DIN rail with spring contact |
Mode state visual indicators | Fault (FLT), status (STS) LED lamps |
Power Supply | |
---|---|
Main power supply VM | 24 V DC (-15% ÷ + 20% according to IEC 61131-2) |
Massimo ripple ammesso | 5% of supply voltage (according to IEC 61131-2) |
Current consumption from main supply | 1.5 A max. (for external loads supply) |
Supply overvoltage protection | Bidirectional Zener clamp (Vz > 30 V) |
Supply reverse polarity protection | Protection diode, and safety fuse |
Power Fuse | 2 A, not replaceable by the user |
Local bus power supply | 5 V DC (from local bus) |
Local bus supply protections | None |
Power presence visual indicators | Green LED lamp, lighted if main supply is present (PWR) |
Max. current on VS pin | 1.5 A max. |
Analog outputs | |
---|---|
Number of outputs | 2, |
Voltage output range (unidirectional outputs) | 0-10 V |
Voltage output range (bidirectional outputs) | -10V ÷ +10V |
Digital Resolution | 12 bit |
Output permissible load | 1 kΩ a ∞ |
Unidirectional outputs error | t.b.d. |
Bidirectional outputs error | t.b.d. |
Unidirectional outputs temperature coefficient | t.b.d. |
Bidirectional outputs temperature coefficient | t.b.d. |
Output settling time for full-range change | < 1 ms |
Outputs common potential isolation from GND | 500 VAC, functional |
Isolation between channels | None |
Output state visual indicators | Two orange LED lamps for every input, switched on if output 0-10V (UPx) or output ±10V (BPx) is active |
Interface | |
---|---|
Local bus | Proprietary F3 IOs BUS |
Moduli address setting | With rotary switch on front panel |
Bus connessions | By TBUS connectors on DIN rail |
Interface circuitry protections | ESD protections |
Level of ESD protection | ±8 kV (IEC 61000-4-2, contact discharge) |